Loading
/custom-emojis/emojis/contour-map.png
Templates
📚
Articles & Resources
📖
Guides & Support
🌵
CalcTree
Estados de Vigas de Concreto
Bust Common Myths About Java Programming
Loading
/custom-emojis/emojis/calculator.png
Tensile Strength and Capacity Control of the W-Shape Sections According to AISC 360-16
Loading
/custom-emojis/emojis/calculator.png
Concrete Cylinder Strength Vs Cube Strength
Loading
/custom-emojis/emojis/calculator.png
Earthquake Design Action Calculation
Sıvılaşma Verileri Tablosu
Loading
/custom-emojis/emojis/rc-beam.png
Concrete Column Designer to AS3600
EM Wave Propagation Calculator
section properties with units
Forward Kinematics of Robotic Arm with 6 Degrees of Freedom
İKSA YAPILARI PROJELENDİRME HİZMET BEDELİ (2024)
GEOTEKNİK RAPOR (EK-B) ASGARİ HİZMET BEDELİ (2024)
ZEMİN İYİLEŞTİRME/DERİN TEMEL PROJELENDİRME ASGARİ HİZMET BEDELİ (2024) (İMO)
🚀
Projectile motion
Loading
/custom-emojis/emojis/bending-moment.png
Dezi et. al (2010)
🤾
Projectile motion
Transformer Short Circuit Calculation's banner
/custom-emojis/emojis/cables.png

Transformer Short Circuit Calculation

Welcome to our transformer short circuit calculation! This page will allow you to undertake a transformer short circuit current calculation using the transformer rating in kVa, the voltage rating of the secondary winding and the per unit impedance of the transformer in percentage. Let's begin!

Calculation

Inputs



S, kVA
:10kVA



V (LL)
:435volts



Z %
:10


Output



I (3P)
:0.132728093ampere



I (PP)
:0.114942529ampere



I (PN)
:0.0465698947ampere



I (PE)
:0.0465698947ampere


Z% to find Zn



Z0
:0.085ohms



Z1
:0.1ohms



Z2
:0.1ohms



Explanation

In a transformer, fault current refers to the amount of current that flows through the transformer when there is a fault or short circuit in the system. This current can be much higher than the normal operating current of the transformer. It can cause damage to the transformer and other electrical equipment if it is not properly protected.
Several types of fault conditions can occur in a transformer, such as a short circuit between the primary and secondary windings, a short circuit between the windings and the transformer's core, or an external short circuit on the secondary side of the transformer. Each of these fault conditions can result in a different fault current magnitude and waveform.

💡Understanding and analysing these fault currents is important to properly design and protect the transformer and the electrical system.


3Phasefault(A)=I3P=S3VLLZ13 \: Phase \: fault \: (A)=I_{3P} = \frac {S} {\sqrt{3} \: \cdot \: V_{LL} \: \cdot Z_{1} }

Phasetophasefault(A)=Ipp=SVLL(Z1+Z2)Phase \: to \: phase \:fault \: (A)=I_{pp} = \frac {S} {V_{LL} \cdot (Z_{1} \: + \: Z_{2} )}

Phasetoneutralfault(A)=Ipn=3S3VLL(Z0+Z1+Z2)Phase \:to \:neutral \: fault \: (A)=I_{pn} = \frac {3 \cdot S } { \sqrt {3} \cdot V_{LL} \cdot (Z_{0} + Z_{1} + Z_{2} ) }

Phasetoearthfault(A)=Ipe=3S3VLL(Z0+Z1+Z2)Phase \: to \: earth \: fault \: (A)=I_{pe} = \frac {3 \cdot S} { \sqrt{3} \cdot V_{LL} \cdot (Z_{0} + {Z_{1} + Z_{2} ) } }

Where:

S=TransformerRating(kVA)VLL=VoltageRating(V)Z%=PerunitimpedanceofTransformerZ0=ZeroSequenceImpedance(Ω)Z1=PositiveSequenceImpedance(Ω)Z2=NegativeSequenceImpedance(Ω) \\S = Transformer \: Rating \: (kVA) \\ V_{LL} = Voltage \: Rating (V) \\ Z \% = Per \: unit \: impedance \: of \: Transformer \\ Z_{0} = Zero \: Sequence \: Impedance \: (Ω) \\ Z_{1} = Positive \: Sequence \: Impedance \: (Ω) \\ Z_{2} = Negative \: Sequence \: Impedance \: (Ω)

Zero, Positive and Negative Sequences (Zn)

👉 Important note!