This calculator computes the shear capacity of a suspended flat slab at a concentrated load. This situation is often referred to as 'Punching Shear'.
All calculations are performed in accordance with AS 3600:2018.
Calculation
Refer to the diagrams in the toggle below to illustrate the parameters used in this calculator.
Punching shear diagrams in AS3600 Section 9.3
AS 3600:2018 - Figure 9.3(A)
AS 3600:2018 - Figure 9.3(B)
AS 3600:2018 Figure 9.3.6
Inputs
Open each toggle block below to input required values.
Slab Properties
Input value
Parameter description
f'c
:50MPa
Characteristic concrete strength
Ds
:250.00mm
Overall depth of slab
c
:40mm
Cover to bottom reinforcement
db
:20mm
Bar diameter of bottom layer reinforcement
fcv
:1.9233304448274107MPa
Concrete shear strength
dom
:200mm
Mean value of
do
, averaged around the critical shear perimeter.
do
is the effective depth of the concrete section. This calculator assumes that the concrete slab/beam depth is the same on all sides surrounding the concentrated load.
u
:2000mm
Length of the critical shear perimeter
Manual input of 'u' value?
:Yes
u (auto)
:2000mm
u (manual)
:2000mm
u
is automatically calculated in specific cases only where the arrangement of load shapes and critical penetrations are simple. Select 'Yes' for manual input of
u
if you only want to use
u(manual)
parameter. If you select 'No' then the calculator will determine if
u(auto)
can be used.
a
:1200mm
Refer Figure 9.3(B), dimension of the critical shear perimeter measured parallel to the direction of
M∗v
.
Design selections
All of these design selections will affect the final shear capacity.
M*v is zero
:Yes
Dimension parallel to M*v
:Y
Shear head/drop panel provided
:No
TS or SB
:TS
💡Note
Shear reinf in slab?
:No
💡Note
Load near a slab edge?
:C
💡Note
If chosen 'E' above, which dimension of load is parallel to slab edge?
:X
Load shape rectangular?
:Yes
💡Note
Column Details
Refer to Figure 9.3(A).
X
:300mm
Y
:1000mm
Dimensions of concentrated load i.e. the column.
Ultimate Design Loads
V*
:50kN
Ultimate design shear load at the location under consideration
M*v
:10kN m
Ultimate design bending moment transferred from the slab to the support in the direction being considered
The following inputs are optional if they apply to the slab design being considered. If they are not applicable, they can be left as is or set to zero.
Critical Penetration Details (if applicable)
The opening may be considered a critical penetration, depending on the opening's distance from the concentrated load and size of the opening.
bo
:200mm
Dimension of an opening. Refer to Figure 9.3(A).
l1
:360mm
Distance of opening from the concentrated load being considered
2.5 bo
:500mm
Critical distance for an opening to be considered a critical opening
l1 - dom/2
:260mm
Check if opening is within critical distance.
Critical
:Yes
If yes, the opening is considered critical and will affect calculation of 'u'. If there is a critical penetration, please provide a manual value for 'u'.
Can’t display the image because of an internal error. Our team is looking at the issue.
Spandrel Beam Details (if applicable)
Refer to Figure 9.3.6.
Db
:450mm
Depth of beam
bw
:300mm
Effective width of beam
x
:300mm
y
:500mm
Required for calculation of
Vu.max
. Lowercase
x
and
y
are the shorter and longer dimensions respectively of the cross-section of the torsion strip or spandrel beam.
If prestress is present, provide the effective stress at the location being considered. Otherwise input
σcp=0.
Outputs
The critical shear perimeter and shear capacity is provided for every type of situation, regardless of the user input, see toggles below.
Calculated
u
Values
Calculations for
u
based on load position relative to slab edges (for rectangular or square load shapes only).
u (I)
:3400mm
Critical shear perimeter for an internal load with no critical slab penetrations or edges
u (E-X)
:2900mm
Critical shear perimeter where the slab edge is parallel to the 'X' dimension of the load
u (E-Y)
:2200mm
Critical shear perimeter where the slab edge is parallel to the 'Y' dimension of the load
u (C)
:1700mm
Critical shear perimeter for a load near the corner of a slab
u final
:1700mm
Final critical shear perimeter based on user's Design Selections
Slab Shear Capacity when
M∗v
is zero
Vuo
refers to the unfactored shear strength.
Vuo
:769.332177930964kN
Eq 9.3.3(1) No shear head
Vuo (SH)
:1414.2135623731kN
Eq 9.3.3(2) With shear head (SH)
Slab Shear Capacity when
M∗v
is not zero
Vu
refers to the unfactored shear strength. TS is Torsion Strip and SB is Spandrel Beam.
Vu (1)
:769.1719337780961kN
Eq 9.3.4(1) No closed fitments
Vu.min (TS)
:923.070409293643kN
Eq 9.3.4(2) TS with min closed fitments
Vu.min (SB)
:1660.8348183206945kN
Eq 9.3.4(3) SB with min closed fitments
Vu (TS)
:3732.9230607056948kN
Eq 9.3.4(4) TS with more than min closed fitments
Vu (SB)
:6716.463371495656kN
Eq 9.3.4(4) SB with more than min closed fitments
Vu.max
:NAkN
Eq 9.3.4(5) Max shear capacity in all cases
The shear capacity relevant to your slab design is provided in the toggle below.
Slab Shear Capacity (Punching Shear Capacity),
ϕVu
∅
:0.75
Capacity reduction factor, refer to Table 2.2.2 in AS3600:2018
Vu
:769.332177930964kN
Unfactored final shear capacity
∅Vu
:576.999133448223kN
Factored final shear capacity
Utilisation
:0.08665524279246903
PASS/FAIL
:PASS
Explanation
What is punching shear?
Punching shear is a failure mechanism in structural members like slabs and foundations by shear under the action of concentrated loads, such as columns.
Punching shear failure mechanism
In analysis we are only concerned about the load that is transferred to the column at the slab level in consideration. That is, do not include the axial forces in the column above this level.
Punching shear zones on a traditional concrete flat slab
How do I design for punching shear?
Punching shear capacity of a slab is dependent on the assumed failure length, also known as the "critical shear perimeter" or "punching shear surface". This is the perimeter of a shape formed by outlining the loaded area with a clear gap of
dom/2
, refer Figure 4.16 of AS3600.
Critical shear perimeter (or punching shear surface) shown in (a) isometric and (b) section
The calculation method adopted for punching shear design depends on whether any moment,
M∗v
is being transferred from the slab to the support in the direction being considered. This calculator considers situations where
M∗v
is zero and non-zero.
The applicable sections of AS3600 are Section 9 (Design of slabs for strength and serviceability) and Section 9.3 (Strength of Slabs in Shear). See the toggles below for the code formulas used in this calculator.