Verified by the CalcTree engineering team on August 30, 2024
This calculator performs the analysis and design of reinforced concrete two-way spanning slabs supported by columns, i.e. a flat slab. Design actions are calculated using simplified elastic analysis. Flexural capacity and deflection are then checked.
All calculations are performed in accordance with AS3600-2018.
Calculation
Technical assumptions
Slab Properties
RC slab cross-section
Geometry:
B
:1.00 m
D
:225 mm
Ly
:5.00 m
Lx
:4.00 m
Ly / Lx
:1.25
Slab_type
:Two-way
One- or two-way slab
Concrete Properties:
fc
:32MPa
Ec
:30,100
Density_c
:25 kN / m^3
Reinforcement Properties:
fsy
:500 MPa
Es
:200 GPa
Reinf in tension zone:
db_st
:16mm
s_st
:200 mm
c_st
:25 mm
d_st
:192 mm
Ast
:1,005 mm^2
Reinf in compression zone:
db_sc
:10mm
s_sc
:200 mm
c_sc
:25 mm
d_sc
:30 mm
Asc
:393 mm^2
Loads
SW
:5.63 kPa
SDL
:0.50 kPa
Q
:2.00 kPa
Fd
:10.35 kPa
ULS
psi_s
:0.7
psi_l
:0.4
kcs
:1.18
F_def, total
:15.7 kPa
F_def, incr
:9.6 kPa
SLS
Slab Analysis
For two-way slabs supported by columns, as per Clause 6.10.4.
Mo=8FdLtLo2
Mo, interior x
:103.5 kN m
Mo, interior y
:129.4 kN m
Mo, edge y
:64.7 kN m
Mo, edge x
:51.8 kN m
4x unique
Mo
per flat slab system
Mcritical section∗={+Mmid span∗,−Minterior or exterior edge∗}=factor×Mo
Factor is given in Tables 6.10.4.3(A) & (B)
Exterior_edge_restraint
:Restrained by spandrel beams and columns
Mcolumn strip∗=column strip moment factor×Mcritical section∗Mmiddle strip∗=(1−column strip moment factor)×Mcritical section∗
Column strip moment factor is given in Table 6.9.5.3
Neg_moment_at_interior_support
:0.6
Pos_moment_at_all_spans
:0.6
Neg_moment_at_exterior_support
:0.75
Slab analysis
M∗
results:
Can’t display the image because of an internal error. Our team is looking at the issue.
Can’t display the image because of an internal error. Our team is looking at the issue.
Slab analysis breakdown
❗Ensure these conditions have been met
For flat slabs, the simplified elastic analysis as outputted above is valid if:
Q<2G
, where Q = live load & G = dead load
loads are uniformly distributed
at least two continuous spans in each direction
support grid is roughly rectangular
successive span lengths in each direction do not differ by more then 1/3 of the longer span, and the end span cannot be longer then the adjacent interior span
M∗
at supports are only caused by loads applied to the beam or slab, not from the columns
Flexural (ULS) Design Check
phi
:0.85
Capacity reduction factor
ku
:0.11
Check ku
:< 0.36 ✅
Ductility check
Ast,min
:430 mm^2
Check Ast
:> Ast,min ✅
Minimum reinforcement check
α2
:0.80
γ
:0.89
Mu
:77.8 kN m
+M*_max
:38.8 kN m
-M*_max
:-54.3 kN m
Moment capacity check
Check +M*
:= 39kNm ≤ Mu = 78kNm, OK ✅
Check -M*
:= 54kNm ≤ Mu = 78kNm, OK ✅
Note
For sagging moment
(+M∗)
,
Ast
is on the bottom &
Asc
on the top
For hogging moment
(−M∗)
,
Ast
is on the top &
Asc
on the bottom
Deflection (SLS) Check
Slab type
:Ly/Lx = 1.25 ∴ Two-way slab supported by Columns
Span_type
:Simply supported
Drop_panels
:Yes
k3
:1.05
k4
:1.40
Lef / d
:26
Simplified approach
For total deflection:
Deflection_limit_total
:1/250
(Lef / d)_limit
:29
Check
:Lef/d ≤ limit ✅
Min D
:205 mm
For incremental deflection:
Deflection_limit_incr
:1/500
(Lef / d)_limit (1)
:27
Check (1)
:Lef/d ≤ limit ✅
Min D (1)
:217 mm
❗Ensure these conditions have been met
As per Clause 9.4.4, for RC slabs, the simplified approach for flat slab deflection is valid if:
loads are uniformly distributed
Q≤G?
check
:Q = 2.0kPa ≤ G = 6.1kPa, simplified analysis is valid ✅.
uniform slab depth
fully propped during construction
for flat slabs with drop panels, drop panels must extend at least
L/6
in each direction on each side of the support centre-line, and have an overall depth not less then
1.3×
slab thickness beyond the drops
in adjoining spans, the ratio of the longer span to the shorter span does not exceed